300kW Diesel Generator
300kW fixd diesel generating set technical performance
function index
Use of performance characteristics:
1.High quality engine,
2.Choosing Faraday generator.
3.With automatic control system, operation control system and the automatic switching system, can clearly and accurately reflect the unit running in various state parameters, 4.Intelligent control system provides a higher security, greatly improve the reliability of machine system.
5.Its compact structure, stable running, convenient maintenance, and can be widely used in military, aerospace, communications, transportation, oil, construction and other industries as the main and emergency power supply.
The main performance index:
Use of the environment
Altitude: < 1000M
Degree earthquake intensity: 8
Environment temperature: - 5C to + 40 C (Celsius)
Relative humidity: 90% (25 degrees C ) no coagulation
No explosive gas, no conductive dust.
Main rating data
Rated power: 300kW
Rated voltage: 400 / 230VAC
Rated current:540A
Rated frequency: 50Hz
Rated power factor: 0.8 ( lag )
Rated speed: 1500r / min
Phase: phase four wire
Weight ( kg ): 3400
Size ( mm ): 3300×1140×1800
Main performance index
Steady state voltage deviation: ≤±1%
Transient voltage deviation: ≤+ 15% ( anticlimax 100% load ) ≥ -15% ( load 50% load )
Voltage recovery time: ≤2S
Voltage unbalance degree: ≤1%
Line voltage waveform distortion rate: 5%
Frequency down: ≤2%
Steady state frequency band: less than 1%
Transient frequency deviation: ≤ 10% ( anticlimax 100% load ) ≥ - 7% ( load 50% load )
Frequency recovery time: ≤2S
Steady state frequency rang: 1%
300kW Diesel Generator